Method Statement for Electrical Work — UK

Free UK electrical method statement template, aligned with the Electricity at Work Regulations 1989, BS 7671:2018+A2:2022 (18th Edition Amendment 2) and the HSE Safe Isolation Procedure (SfI).

UK (RAMS) example document — Two-Storey Rear Extension — 14 Birchwood Lane, Reading. Client: Mr & Mrs A. Whitfield (Private Client). Site: 14 Birchwood Lane, Reading, RG1 5JT. Scope: Construction of a two-storey rear extension (6.4m × 4.2m) to an existing semi-detached dwelling. Works comprise breaking out of existing rear elevation, trench-fill foundations to 1.0m, traditional cavity blockwork to first floor, pre-stressed concrete lintels, timber roof structure with natural slate finish, plus alterations to existing rear wall to form structural opening with rolled steel joist (RSJ 203×102 UB23). Works programmed over 9 weeks with a peak site team of 6 operatives. Hazards assessed: Manual handling — blocks, lintels, plasterboard, Working at height — independent scaffold & roof structure, Buried services strike during excavation, Collapse of excavation / trench wall, Hand-arm vibration (HAVS) — breaking out, drilling, Silica dust — cutting blocks, brick, concrete, Vehicle/pedestrian segregation — narrow domestic street.

Example UK (RAMS) front cover produced by Riskora
Try the new compact mode. Same document, just more compact

Full version

Preview first. No card needed. Download when you're happy.

  • Site-specific draft
  • Electrical Work hazards baked in
  • Ready for competent-person review

Built around recognised UK method statement structure — hazards, controls, sequence, PPE and sign-off. Ready for competent-person review.

The Electricity at Work Regulations 1989 reg. 14 sets the strictest principle in UK occupational law: 'No person shall be engaged in any work activity on or so near any live conductor … that danger may arise unless (a) it is unreasonable in all the circumstances for it to be dead.' The default is dead working. A defensible electrical method statement names the isolation method, the lock-off-tag-out (LOTO) sequence, the proving dead (HSE GS38 voltage indicator), and only then — if live working is genuinely justified — names the live-working risk assessment and PPE. Anything less is non-compliant.

When is it required?

A written MS is required for any electrical installation, maintenance or test work under EAWR 1989 and CDM 2015. NICEIC, NAPIT and SELECT (Scotland) require their members to issue a method statement and risk assessment for any non-trivial electrical work. For live working, a separate live-working justification document (LWJD) is required, signed by a senior competent person, naming why dead working is impracticable. BS 7671 is the technical standard for the installation; the MS is the safety document for the people doing it.

What a good one looks like

A defensible electrical MS names the operative's competence (City & Guilds 2391/2/3, JIB Approved Electrician, ECS card class), the isolation point (e.g. 'MCCB DB-3 way 12, locked with personal padlock'), the test equipment (e.g. 'Megger DCM340 voltage indicator and proving unit, calibrated 2026-03-14') and the safe isolation sequence (Test → Isolate → Lock → Tag → Prove dead → Prove the voltage indicator still works → Begin work). It includes a defined sign-off sequence on completion (Reverse: Restore → Test → Energise → Verify → Hand over with EIC) and arrangements for the second person where work is in a high-risk environment. Live-working clauses are only present if a LWJD has been completed.

Electrical Work hazards & controls

The site-specific hazards a electrical MS must address, with the controls that take residual risk to an acceptable level.

HazardPersons at riskControlsResidual
Electric shock from inadvertent contactElectrician, others nearbySafe isolation per HSE Electrical Safety Procedure; LOTO with personal padlock; proving dead with GS38 voltage indicator; proving the indicator works before and after; second person where requiredLow
Arc flash during switchingElectrician, anyone within arc zoneArc-rated PPE (face shield + flame-retardant overalls) for any switching on industrial supplies; switching from side of cabinet (not in front); coordinated by senior competent personLow
Inadvertent re-energisationElectricianPersonal padlock + tag with name + date; single-key system; multi-lock hasp where multiple trades affected; key held by working operative onlyLow
Working at height (DB / ceiling-level cabling)ElectricianTower scaffold or MEWP for >2m work; no ladder for work; competence card (PASMA / IPAF) namedLow
Manual handling - cable drums (50-500+ kg)Cable pullers, labourersMechanical drum stand; pulling winch for runs >25m; no manual lift of drums >25kg without mechanical aidMedium
Fire from arc / overheated cableAll on siteHot works permit for any soldering or torching; CO₂ extinguisher within 5m of switching; no flammable storage near LV switchgear; cable sizing per BS 7671 to avoid overheatingLow
Asbestos in older switchgear / boardsElectrician, other tradesPre-2000 boards treated as potentially containing asbestos until R&D survey confirms; UKATA awareness for all operatives; specialist removal if foundLow
Confined space (cable pits, ducts)Electrician enteringPermit-to-enter; atmospheric test; forced ventilation; standby man; rescue equipment per Confined Spaces Regs 1997Low

Step-by-step sequence

  1. 1

    1. Permit-to-work / isolation request

    Liaise with duty-holder; obtain permit-to-work or isolation request; circuit identified and verified against schedule.

  2. 2

    2. Safe isolation (Test → Isolate → Lock → Tag → Prove → Re-prove)

    Test the voltage indicator on a known live source; isolate at the named isolator; lock with personal padlock; tag with name + date + circuit; prove dead at point of work; re-prove the indicator on a known live source.

  3. 3

    3. Work activity

    Carry out installation / maintenance / fault-find per BS 7671 and the design drawings. Materials handled per manual-handling controls; cable pulling with winch where appropriate.

  4. 4

    4. Testing & inspection

    Test per BS 7671 Part 6: continuity, insulation resistance, polarity, earth fault loop, RCD operation. Results entered on EIC/MEIWC.

  5. 5

    5. Re-energisation

    Remove lock and tag (key holder only); re-energise at named isolator; verify supply present at point of work; verify under-load operation.

  6. 6

    6. Handover

    EIC or MEIWC issued to duty-holder; circuit schedule updated; warning notices fitted (RCD test, distribution board); residual risks briefed to occupier.

  7. 7

    7. Live working (only if LWJD signed)

    Separate live-working risk assessment; arc-rated PPE; insulated tools; second competent person present; rescue plan; documented in the works pack.

  8. 8

    8. Records

    All certificates, test results and LWJDs retained for 6 years (or duration of installation). Lock-off keys returned to register.

Worked example

Real example — DB replacement, occupied office (Reading)

A NICEIC-approved contractor in Reading is replacing a 1990s 12-way TPN distribution board with a new 18-way TPN board in an occupied office. The MS names the operative (JIB Approved Electrician, ECS Gold, C&G 2391 valid 2027), the duty-holder (the office facilities manager) and the second person (also an Approved Electrician). Pre-start: an out-of-hours shutdown agreed for 18:00 Friday — Sunday 18:00. Safe isolation sequence: incoming MCCB located in the riser cupboard; the voltage indicator (Megger DCM340, calibrated 2026-03-14) is proved against a known live socket; incoming MCCB switched off; personal padlock + tag fitted; circuit at the DB proved dead with the indicator; the indicator re-proved against the known live source. The old DB is removed; the new DB fitted; circuits re-terminated to the schedule (verified live-to-live with continuity tester); ferrules and circuit identification labels fitted. Testing per BS 7671 Part 6: continuity (R1+R2), insulation resistance to 500V DC (>1 MΩ each circuit), polarity, earth fault loop impedance, RCD test (5In/100ms). Results entered on the EIC. Re-energisation: padlock removed (key holder only), MCCB switched on, supply verified, under-load operation tested with cleaners' equipment on Sunday evening. Hand-over to facilities Monday 07:30 with EIC, updated schedule and RCD-test notice fitted. MS runs to 12 pages with the test certificate template appended.

Or build a site-specific electrical MS in 5 minutes

The free template is a blank Word document. The Riskora builder ships with the electrical hazard library baked in — pick the preset, edit the site-specific bits, download a signed PDF.

Common mistakes that get a electrical MS rejected

  • ·'Isolate, check with screwdriver, work' — without a GS38-compliant indicator + proving unit
  • ·No personal padlock — relying on a sticker or another trade's lock
  • ·Live working with no LWJD signed by a senior competent person
  • ·Voltage indicator not proved on a known live source before and after
  • ·Older switchgear opened without an R&D asbestos survey
  • ·Test results not recorded on an EIC / MEIWC — installation handed over with no certificate

Frequently asked questions

Can I work live on UK electrical systems?

Only if you have a signed live working justification document (LWJD) explaining why dead working is impracticable, signed by a senior competent person. EAWR 1989 reg. 14 sets dead working as the default; live working is the exception, not the rule.

What is 'safe isolation' in the HSE procedure?

Test the voltage indicator on a known live source → isolate at the named isolator → lock with a personal padlock → tag → prove the circuit is dead at the point of work → prove the voltage indicator still works on a known live source. All six steps, in that order, every time.

Who is a 'competent person' for electrical work?

Defined in EAWR 1989: someone with adequate technical knowledge, training and experience for the specific work, including knowledge of the hazards and the precautions. In practice, JIB Approved Electrician / ECS Gold / C&G 2391 for testing — but always specific to the work in front of them.

Do I need a second person?

Required where the risk assessment identifies that one cannot safely work alone — typically live working, work at height, confined space entry, isolation of complex switchgear. The MS must name the second person and their role.

What's the difference between an EIC and a MEIWC?

An EIC (Electrical Installation Certificate) is issued for any new installation or major alteration. A MEIWC (Minor Electrical Installation Works Certificate) is for minor work — e.g. adding a single socket — that does not introduce a new circuit.

How long must electrical certificates be retained?

For the life of the installation, ideally — and certainly long enough to cover any periodic inspection (typically 5 years for commercial). Contractors retain a copy for at least 6 years (Limitation Act 1980) for any potential claim.

Download the template, or build it in 5 minutes

Riskora is an assistive document preparation tool. Every method statement must be reviewed and signed by a competent person before use.